UPS & BATTERY TESTING
Testing a UPS (Uninterruptible Power Supply) battery is essential to ensure reliable backup power during outages. Here's how to properly test a UPS battery:
1. Visual Inspection
Check for swelling, leakage, or corrosion.
Verify connections are clean and tight.
2. Battery Runtime Test (Load Test)
Disconnect non-critical loads.
Plug in a device (e.g., lamp or small computer) that draws a known load.
Unplug the UPS from the wall (simulate a power outage).
Monitor how long the UPS runs before shutting down.
Compare the runtime with manufacturer specs. If it's significantly shorter, the battery may be degraded.
3. UPS Self-Test
Most modern UPS systems have a built-in self-test function:
Press and hold the test or power button (refer to the manual).
The UPS will simulate a power failure and run diagnostics.
Check the status LEDs or display for results (e.g., 'Battery Good' or error codes).
4. Voltage and Internal Resistance Test (Advanced)
Use a multimeter and/or battery tester:
Fully charge the UPS.
Measure voltage across the battery terminals:
For a 12V SLA battery: should be around 12.6–13.0V at rest.
Under load, should not drop below 10.5V.
Use a battery analyzer to check internal resistance (higher resistance = aging battery).
5. Monitoring Software
Many UPS units can connect via USB to a PC.
Use manufacturer software (e.g., APC PowerChute, Eaton UPS Companion) to check:
Battery health
Last self-test results
Charge level and runtime estimate
When to Replace the Battery
Battery fails load or self-test
Noticeable decrease in runtime
Voltage drops quickly under load
Age exceeds 3–5 years (typical lifespan for lead-acid batteries)
Keywords
runtime estimate
wall simulate
load unplug
properly test
leadacid batteries
manufacturer software
ups units
status leds
significantly shorter
manufacturer specs
ups runs
small computer
swelling leakage
outages heres
battery analyzer
battery terminals
battery good
power failure
ups measure voltage
modern ups systems
check battery health
12v sla battery
power button refer
power outage monitor
selftest noticeable decrease
run diagnostics check
corrosion verify connections